38AUQ Gemini® Commercial Split System Heat Pump
Commercial Split System Heat Pump
with Puron® Refrigerant
6 to 20 Nominal Tons
The Gemini® 38AU series outdoor units and matched with the 40RU series indoor air handlers offer a wide variety of options for your HVAC application needs. This series is designed for long dependable operation whether it's a rooftop or on-the-ground installation. All GEMINI 38AU Condensing Units and 40RU Fan Coils use environmentally sound Puron® refrigerant. Together, they create a reliable split system that provides easy solutions to a wide range of commercial HVAC needs.
Performance Features
- 38AUQ Heat Pump EERs up to 11.0 and 3.5 COP
- ASHRAE 90.1 Efficiency Compliant
- Standard crankcase heater
- Compressor vibration isolation
- Low ambient temperature control
- Unit performance certified in accordance with ARI standard 340/360
Reliability Features
- High and low-pressure switches
- Anti-short cycling protection
- Prepainted, galvanized steel cabinets that passes 500-hour salt-spray test
- Compressor overload protection
- Scroll compressor
- E-Coat coil protection
- UL, UL, Canada or ETL approved
Installation Features
- Shipped with Puron (R-410A) refrigerant partial charge
- Single-piece design
- Perimeter base rail with forklift slots and lifting holes facilitates rigging
- Suitable for mounting on the ground or the rooftop
- 24V control circuit transformer permits quick, easy wiring of thermostats
Maintenance Features
- Comfort Alert™ diagnostic board
- Powered and non-powered 115-v convenience outlet
- Compressor access panel with easy grip handle
- Easy starting, no-strip screw feature
- Non-fused disconnect switch
Standard Limited Warranty
- 5 years parts only on compressor
- One year parts only on all other parts
38AUQ/40RUQ AHRI Cooling Ratings
Unit | Cooling Stages | Nominal Capacity (Tons) | Net Cooling Capacity (MBH) | Total Power (kW) | EER | IEER |
---|---|---|---|---|---|---|
38AUQ07 / 40RUQ07 | 1 | 6 | 70.0 | 6.4 | 11.0 | 12.6 |
38AUQ08 / 40RUQ08 | 1 | 7.5 | 89.0 | 8.1 | 11.0 | 12.0 |
38AUQ12 / 40RUQ12 | 1 | 10 | 112.0 | 10.2 | 11.0 | 12.0 |
38AUQ16 / 40RUQ16 | 2 | 15 | 178.0 | 16.8 | 10.6 | 11.0 |
38AUQ25 / 40RUQ25 | 2 | 20 | 220.0 | 20.8 | 10.7 | 11.0 |
38AUQ/40RUQ AHRI High Heat Ratings at 47°F (8°C)
Unit | Heating Stages | Nominal Capacity (Tons) | Net Cooling Capacity (MBH) | Total Power (kW) | COP |
---|---|---|---|---|---|
38AUQ07 / 40RUQ07 | 1 | 6 | 66.0 | 5.9 | 3.30 |
38AUQ08 / 40RUQ08 | 1 | 7.5 | 87.0 | 7.7 | 3.30 |
38AUQ12 / 40RUQ12 | 1 | 10 | 106.0 | 9.4 | 3.30 |
38AUQ16 / 40RUQ16 | 2 | 15 | 178.0 | 15.3 | 3.40 |
38AUQ25 / 40RUQ25 | 2 | 20 | 214.0 | 17.9 | 3.50 |
38AUQ/40RUQ AHRI Low Heat Ratings at 17°F (-8°C)
Unit | Heating Stages | Nominal Capacity (Tons) | Net Cooling Capacity (MBH) | Total Power (kW) | COP |
---|---|---|---|---|---|
38AUQ07 / 40RUQ07 | 1 | 6 | 39.0 | 5.2 | 2.20 |
38AUQ08 / 40RUQ08 | 1 | 7.5 | 52.0 | 6.9 | 2.20 |
38AUQ12 / 40RUQ12 | 1 | 10 | 70.0 | 9.3 | 2.20 |
38AUQ16 / 40RUQ16 | 2 | 15 | 108.0 | 13.2 | 2.40 |
38AUQ25 / 40RUQ25 | 2 | 20 | 130.0 | 15.9 | 2.40 |
LEGEND
AHRI = Air-Conditioning, Heating and Refrigeration Institute
ASHRAE = American Society of Heating, Refrigerating and Air Conditioning, Inc.
EER = Energy Efficiency Ratio
IEER = Integrated Energy Efficiency Ratio
COP = Coefficient of Performance
NOTES
1. Rated in accordance with ARI Standard 340/360---07, as appropriate.
2. Ratings are based on:
- Cooling Standard: 27°C (80°F) db, 19°C (67°F) wb indoor air temp and 35°C (95°F) db outdoor air temp.
- IEER Standard: 27°C (80°F) db, 19°C (67°F) wb indoor air temp and 4 various outdoor temperatures.
3. All units comply with ASHRAE 90.1 Energy Standard for minimum EER and IEER requirements.
Factory-Installed Options
- Non-fused Disconnect
- Premium, E-coated condenser coil
- Convenience outlet (powered)
- Low ambient temperature Motormaster® control
- Louvered hail guards
Field-Installed Accessories
- Low ambient temperature Motormaster® control
- Louvered hail guard
- Programmable thermostats