Single-Packaged Rooftop Units High-Efficiency Heat Pump Puron® (R-410A) Refrigerant
3 to 10 Nominal Tons
WeatherMaster® 50HCQ rooftop units were designed to be easy to install, maintain, and operate, with customer-requested features including a gage port, centralized control center, plug-and-play accessory board, "no-strip screw" collars, and handled access panels. Units are field-convertible to horizontal airflow without special adapter curbs or kits, making it easy for the installer to adjust to unexpected jobsite complications. Units are pre-wired and pre-charged with environmentally sound Puron (R-410A) refrigerant and are factory tested.
Performance Features
ASHRAE 90.1 and Energy Star compliant
Single-stage capacity control (sizes 04 to 07)
Two-stage cooling capacity control (sizes 08 to 12)
Up to 15.8 SEER, 13.0 IEER, 12,1 EER, 8.2 HSPF, and 3.5 COP
Cooling operating range up to 125°F (52°C) and down to 30°F (-1°C) on size 04 to 14 units or down to 30°F (-1°C) on size 16 and 24 units
Exclusive non-corrosive composite condensate pan in accordance with ASHRAE 62 Standard, sloping design; side or center drain
Pre-painted exterior panels and primer-coated interior panels tested to 500 hours salt spray protection
Maintenance Features
Control terminal board facilitating simple safety circuit troubleshooting and simplified control box arrangement
Access panels with easy grip handles and tool-less filter access door
Innovative, easy starting, no-strip screw feature on unit access panels
Tool-less filter access door
Belt drive evaporator-fan motor and pulley combinations available on all three phase models to meet any application
Electric Drive x13 (5 speed/torque) motor on 04 to 06 models
Two-inch disposable return air filters
Installation Features
Same footprint as installed Carrier 3-10 ton rooftops back to 1989, reducing installation costs and time
Field convertible from vertical to horizontal airflow for slab mounting (sizes 04 to 14)
Provisions for thru-the-bottom power entry capability as standard
Single point electric and control connections
Full perimeter base rail with built-in rigging adapters and fork truck slots
Reliability Features
Scroll compressors with internal line-break overload protection
Compressor crankcase heaters (sizes 05 to 12)
24-volt control circuit protected with resettable circuit breaker
Permanently lubricated evaporator-fan motor
Totally enclosed condenser motors with permanently lubricated bearings
Loss of charge, freeze protection, and high-pressure switches
Dependable time/temperature defrost board and logic
Standard Limited Warranty
5-year parts only on electric heater
5-years parts only compressor
1-year parts only on other parts
Extended warranty packages available
Nominal Cooling Ton Size
Cooling Stages
AHRI Efficiency (SEER) EER
Dimensions (in) LxWxH
At 47°F
At 17°F
Unit Weight (lbs)
Heating Capacity (Btuh)
(HSPF) COP
Heating Capacity (Btuh)
(HSPF) COP
3
1
(15.6)
74 x 47 x 33
34000
(8.00)
18400
(N/A)
495
4
1
(15.8)
74 x 47 x 41
46000
(8.10)
23800
(N/A)
580
5
1
(15.0)
74 x 47 x 41
55000
(8.20)
28600
(N/A)
610
6
1
12.0
88 x 59 x 41
70000
3.40
39000
2.40
710
7.5
2
12.1
88 x 59 x 49
84600
3.50
47000
2.40
875
8.5
2
12.0
88 x 59 x 49
100000
3.40
56000
2.26
1020
10
2
12.3
116 x 63 x 57
116000
3.50
65000
2.40
1390
LEGEND AHRI = Air-Conditioning, Heating & Refrigeration Institute ASHRAE = American Society of Heating, Refrigerating and Air Conditioning, Inc. EER = Energy Efficiency Ratio SEER = Seasonal Energy Efficiency Ratio
NOTES 1. Rated and certified under ARI Standard 210/240---06 or 340/360---07, as appropriate. 2. Ratings are based on: » Cooling Standard: 80 F (27 C) db, 67 F (19 C) wb indoor air temp and 95 F (35 C) db outdoor air temp. » IPLV Standard: 80 F (27 C) db, 67 F (19 C) wb indoor air temp and 80 F (27 C) db outdoor air temp. 3. All 50HCQ units comply with ASHRAE 90.1 2001, 2004 Energy Standard for minimum SEER and EER requirements. 4. Where appropriate, 50HCQ units comply with US Energy Policy Act (2005). Refer to state and local codes or visit the following website: http://bcap-energy.org to determine if compliance with this standard pertains to your state, territory, or municipality.
Factory-Installed Options
Cabinet
Thru-the-base electrical or gas-line connections
Coil Options
Cu/Cu indoor and/or outdoor coils
Pre-coated outdoor coils
Premium, E-coated outdoor coils
Condenser Protection
Condenser coil hail guard (louvered design)
Controls
PremierLink™ DDC communicating controller
RTU OPEN™ open-protocol controller
Smoke detector (supply and/or return air)
Economizers & Outdoor
EconoMi$er IV (for electro-mechanical controlled RTUs)