Carrier 6 Ton, Heat Pump Indoor Air Handler, 460/3

Item
40RUQA07A2A60A0A0
  • California Prop 65

Packaged Air Handling Units

Heat Pump, 6 to 20 Tons with Puron® Refrigerant (R-410A)

The Gemini® 40RU and 38AU series indoor air handlers and outdoor units provide a wide variety of options for your HVAC application needs. These units are designed for long dependable operation whether it’s a rooftop or on-the-ground installation. All Gemini® 38AU Condensing Units and 40RU Fan Coils use environmentally sound Puron® refrigerant. Together, they create a reliable split system that provides easy solutions to a wide range of commercial HVAC needs.

The 40RU series indoor air handler contains a chilled water coil and may be interfaced into chilled water systems. The 40RU series has a multi-position design that allows for vertical or horizontal installation with no modifications. Powerful fan systems allow easy adaptation to existing ductwork. For heating capability, the 40RU’s allow for field installed electric heaters, hot water coils, or steam coils.

Performance Features

  • Uses field-supplied Puron® (R-410A) refrigerant and chilled water
  • Non-corroding drain pans
  • Cleanable insulation treated with an anti-microbial agent
  • Fan motor options allowing more complex new or replacement air distribution systems
  • Powerful belt-driven forward curved centrifugal fans
  • Durable die-formed galvanized steel casings
  • 40RUQ direct expansion cooling coils are rated in accordance with ARI standard 340/360 when paired with Carrier 38A cooling only condensing units

Reliability Features

  • Precision thermostatic expansion valve (TXV) with removable power element on each circuit
  • Motor overload protection of internal automatic reset thermal overload protection
  • Designed and constructed in accordance with UL 1995 standard
  • Listed with ETL and ETL, Canada

Installation Features

  • Vertical or horizontal installation without modification
  • Simple voltage conversion on tri-voltage 208/230/460-3-60 motors
  • Front or bottom return air intake
  • Two sloped condensate pans for horizontal or vertical applications
  • Simple condensate drain pan adjustment for right-hand or left-hand operation
  • Easy-access 24-volt control terminal block for easy thermostat wiring
  • Single point electrical power connection for fan motor and accessory electrical heaters

Maintenance Features

  • Removable side panel allows access to virtually all components
  • Permanently lubricated, sealed motor bearings
  • Easy filter replacement with slide-out retainer

Standard Limited Warranty

  • One year parts only

38AUQ/40RUQ AHRI Cooling Ratings

UnitCooling StagesNominal Capacity (Tons)Net Cooling Capacity (MBH)Total Power (kW)EERIEER
38AUQ07/40RUQ071670.06.411.012.6
38AUQ08/40RUQ0817.589.08.111.012.0
38AUQ12/40RUQ12110112.010.211.012.0
38AUQ16/40RUQ16215178.016.810.611.0
38AUQ25/40RUQ25220222.020.810.711.0

38AUQ/40RUQ AHRI High Heat Ratings at 47°F (8°C)

UnitHeating StagesNominal Capacity (Tons)Net Cooling Capacity (MBH)Total Power (kW)COP
38AUQ07/40RUQ071666.05.93.30
38AUQ08/40RUQ0817.587.07.73.30
38AUQ12/40RUQ12110106.09.43.30
38AUQ16/40RUQ16215178.015.33.40
38AUQ25/40RUQ25220214.017.93.50

38AUQ/40RUQ AHRI Low Heat Ratings at 17°F (-8°C)

UnitHeating StagesNominal Capacity (Tons)Net Cooling Capacity (MBH)Total Power (kW)COP
38AUQ07/40RUQ071639.05.22.20
38AUQ08/40RUQ0817.552.06.92.20
38AUQ12/40RUQ1211070.09.32.20
38AUQ16/40RUQ16215108.013.24.40
38AUQ25/40RUQ25220130.015.92.40


LEGEND
AHRI = Air-Conditioning, Heating and Refrigeration Institute
ASHRAE = American Society of Heating, Refrigerating and Air Conditioning, Inc.
EER = Energy Efficiency Ratio
IEER = Integrated Energy Efficiency Ratio
COP = Coefficient of Performance

NOTES
1. Rated in accordance with ARI Standard 340/360---07, as appropriate.
2. Ratings are based on:
- Cooling Standard: 27°C (80°F) db, 19°C (67°F) wb indoor air temp and 35°C (95°F) db outdoor air temp.
- IEER Standard: 27°C (80°F) db, 19°C (67°F) wb indoor air temp and 4 various outdoor temperatures.
3. All units comply with ASHRAE 90.1 Energy Standard for minimum EER and IEER requirements.

Factory-Installed Options

  • Unit voltage options:
    • 208/230-3-60
    • 460-3-60
    • 575-3-60
    • 208/230-1-60 (sizes 07 and 08)
  • Staged Air Volume (SAV) Indoor Fan Speed System (sizes 12-25)
  • Alternate fan motors
  • Medium and high-static drives
  • Pre-painted units

Field-Installed Accessories

  • Outside air enthalpy controlled economizer
  • Electric heater
  • Hot water heating coils
  • Steam heating coil
  • Programmable thermostats
  • CO2 sensors
  • Airflow sensor switch
  • Painted and non-painted options:
    • Discharge plenum
    • Return air grille
    • Floor mount subbase
  • Condensate overflow switch assembly
  • Overhead suspension package
Specification
Tonnage 6
Suction Line Size 1 1/8
Suction Line Fitting Flare
Rows/FPI 3
Rows 3
Refrigerant R-410A
Metering Device TXV
Liquid Line Size 5/8
Liquid Line Fitting Flare
Air Flow Configuration Multiposied
Filter Size (4) 16x24x2
Condensate Connection Size 1 5/8 ODM/ 1 1/4 IDF
Coil Type Direct-Expansion
CFM 2,400
Cased Yes
Blower Motor Type Fixed Torque
Blower Motor RPM 1725
Blower Motor HP 2.4
Electrical
FLA 2.6
Hertz 60
MCA 4
MOCP 15
Phase 3
Voltage 460
Safety Standards
California Prop 65 Yes
Weights and Dimensions
Operating Weight (lbs) 399
Exterior Dimensions (D) (inches) 49.000000
Exterior Dimensions (W) (inches) 28.187500
Exterior Dimensions (H) (inches) 56.062500
Shipping Weight (lbs) 450.000000